Solyndra Commercial Complex

Solyndra|Fremont, CA|450 GPM - 35' TDH

jweddell300gpm - 500gpm, Pacific, Stormwater, Stormwater Runoff

This new commercial complex required two new stormwater pump stations designed to meet low flows of runoff. The manholes and hatches were designed at grade to integrate seamlessly with the brick patio and walkway. Submersible centrifugal pumps in a duplex configuration discharge to below grade valve assemblies accessible by valves cans. The UL listed control panels are contained by stainless steel NEMA enclosures and include intrinsically safe barriers. Both lift stations were designed with the same primary components for site standardization.

Los Angeles Trade and Technical College

Los Angeles Trade and Tech College|Los Angeles, CA|600 GPM - 26.2' TDH

jweddell500gpm - 1,000gpm, Pacific, Schools, Stormwater, Stormwater Runoff

The expansion of a college campus required this stormwater pump station to handle medium flows of stormwater runoff. To meet the required pumping rate, 7.5 hp Ebara submersible centrifugal pumps were designed in a duplex configuration. This pumping system was designed with dual force mains and check valves integrated in the discharge piping to simplify the engineering for the system. Romtec Utilities provided the complete electrical engineering plans for the UL listed control panel. Floats for primary and backup liquid level-sensing were supplied to give the system added redundancy.

Walmart in Gardnerville, Nevada

Walmart|Gardnerville, NV|1,300 GPM - 23.4' TDH

jweddell1,000gpm - 5,000gpm, Detention Ponds, Pacific, Parking Lot Drainage, Stormwater, Stormwater Runoff

A new Walmart Supercenter required this package stormwater pump station to handle runoff from its large impervious parking lot. A good sized detention basin collects the runoff water during a storm event, including from surrounding properties. Ebara submersible pumps then empty the detention pond at a high flow rate through just 45’ of force main into a gravity line that flows to treatment. An outdoor UL listed control panel includes float controls for primary and backup liquid level-sensing and a basic alarm for communications.

The Marke Luxury Apartments

The Marke Luxury Apartments|Santa Ana, CA|3,591 GPM - 24.8' TDH

jweddell1,000gpm - 5,000gpm, 100-Year Storm, Mixed Use, Pacific, Stormwater, Stormwater Featured, Stormwater Runoff

This stormwater pump station was designed to handle variable flows of stormwater runoff. The typical stormwater expectations called for low flow pumping, but this pump station needed to handle high flows as well. Two different sizes of submersible centrifugal pumps were used; a 7.5 hp pump and a 25 hp pump. The pumps required differently sized discharge piping and valves for each pump. A PLC control panel handles all lift station functions including starting and stopping on level, SCADA options, an autodialer for communications, and a soft starter for the large pump.

Gas Refinery Process Water

Exxon Mobil|Chalmette, LA|30,000 GPM - Various TDH

jweddell10,000gpm +, Central, Stormwater, Stormwater Runoff

To address the industrial stormwater concerns of coastal Louisiana, this large, precast concrete pump station was designed to meet super-high flows of runoff at this Exxon refinery. Five vertical turbine pumps and three submersible pumps, capable of pumping 60,000 GPM, are spread across three large interconnected rectangular wet wells. This approach was much more affordable than a single poured in place sump, and the connection tubes make the functionality near identical. A robust steel baffle slows incoming stormwater at the inlet line to reduce turbulence and wear on the sump components.