A commercial development in Delaware required this wastewater lift station to handle low flows of sewage from a new fast food restaurant and retail stores. Tsurumi cutter pumps in a duplex configuration macerate solids any in the wastewater to pass through the force main diameter. This lift station pumps a short distance with low head to a nearby gravity collection system that flows to treatment. A UL listed control panel was supplied for complete electrical controls with Nolta Niva floats for in-well liquid level-sensing.
Union Pacific Railroad|Cheyenne, WY|100 GPM - 22' TDH
The Union Pacific Depot in Cheyenne, Wyoming needed two new sewer lift stations to replace its existing sewer collection system. Each lift station included three precast concrete vault structures, a wet well, valve vault, and metering vault. Both systems use 2 hp Ebara Vortex® sewage pumps in duplex configurations that are explosions proof rated for Class I, Division I locations. The valve assemblies comprise Val-Matic Cam-Centric® plug valves and Swing-Flex® check valves with pressure gauges. Endress and Hauser PROline® electromagnetic flow meters measure the sewage flows for both lift stations. These in-ground valve and meter assemblies were fitted with heat tracing to provide reliable frost protection with Raychem and Digitrace components.
Union Pacific Railroad|Cheyenne, WY|4,000 GPM - 25' TDH
The Union Pacific Depot in Cheyenne, Wyoming needed two new stormwater pump stations to replace existing systems. The first station used Ebara 25 hp submersible pumps in a triplex configuration to handle stormwater runoff from a parking lot and additional drains. The second station used Ebara 7.5 hp submersible pumps in a duplex configuration to pump stormwater that drains from the pit of a railway turntable. Both systems include precast concrete valve vaults. Each vault was preassembled with Val-Matic Cam-Centric® plug valves, Val-Matic Swing-Flex® check valves, and Ashcroft pressure gauges. Both stormwater systems discharge into an evaporation pond that was installed as a part of this larger water collection replacement, which also included three additional Romtec Utilities wastewater lift stations.
The City of Camas | Camas, WA | 126 GPM - 206' TDH
In order to expand the municipal sewer system, this lift station was configured to pump to an existing gravity line flowing to treatment. A 24-foot-deep by 10-foot-diameter wet well collects the sewage flows. The wastewater is pumped at 120 gpm 10,000 lineal feet of 10” force main against 206’ TDH with 23 hp high head submersible solids handling pumps. A sheltered control panel utilizes an intrinsically safe barrier for in-well electrical, such as the pressure transducer and conductive probe for primary and backup level controls.
West Mesa Industrial Park|Las Cruses, NM|733 GPM - 44' TDH
The US Army Corps of Engineers worked with Romtec Utilities to design this lift station to replace an existing septic system. The resulting package wastewater lift station met the high sewage flows of this publicly owned industrial complex. The submersible sewage pumps in a duplex configuration are explosion proof to meet the wet well space classification. An outdoor UL listed panel utilizes floats and a pressure transducer for intrinsically safe level controls. It also includes an autodialer for communications and a blower for odor control.